LT Power Cables

6181Y – BS 6004

thumbnail

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded.

conduits and in closed installation ducts. Ideal for internal wiring of appliance.

Standard

EN 50363-3 with BS 7655-4.2 (Only for sheath).

Technical Data

Voltage Rating : 1.5 mmsquare to 35 mmsquare - 300 / 500V

Temperature Range : -15°C to 70 °C

Minimum Bending Radius

Upto 10 mm2 : 10 X Overall Diameter.

16 & 35 mm2 : 12 X Overall Diameter.

16 & 35 mm2 : 12 X Overall Diameter.

Test Voltage : 2 kV for 15 min

Cable Construction

Plain annealed copper conductor : 1.5 & 2.5 mm2 Class -1, 4.0 to 35 mm2 stranded Class 2 complying with BS EN 60228, HD 383, IEC 60228.

Conductor : Plain annealed copper conductor 1.5 mmsquare to 630 mmsquare stranded class 2 complying with BS EN 60228, HD 383, IEC 60228

Insulation : PVC (Polyvinyl Chloride ) compound type TI 1 complying with EN 50363-3

Sheath : PVC (Polyvinyl Chloride ) compound type Type 6 complying with BS 7655-4.2

Insulation Colours : Blue and brown

Sheath Colour :Grey RAL 7001

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 - blue, 09 - brown.

Part Number Nominal Cross Sectional Area (Sq. mm) Nominal Insulation Thickness (mm) Nominal Sheath Thickness (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approx. Net Weight (kg/km)
01150101xx10 1.5 0.70 0.8 4.20 5.00 37
01150102xx10 2.5 0.80 0.8 4.80 5.70 51
01150103xx10 4 0.80 0.9 5.50 6.70 75
01150104xx10 6 0.80 0.9 6.00 7.30 98
01150105xx10 10 1.00 0.9 7.30 8.80 152
01150106xx10 16 1.00 1.0 8.40 10.10 220
01150107xx10 25 1.20 1.1 10.00 12.10 336
01150108xx10 35 1.20 1.1 11.10 13.50 353
Enquire Now